4: View Module List; Zone; 1: Edit Zone - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Zone

8.2.4 View Module List
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Press 1 to enter Module Menu.
4.
Press 4 to View Module List.
8.3 Zone
Through the Zone option in the Program Menu, you can edit and view zone points. Selections made here affect all detectors and switches in
the zone. Up to 250 zones can be used in the system.
8.3.1 Edit Zone
Features that can be edited through the Edit Zone option are zone name, zone properties (which includes, zone type, and detector sensitivity),
zone output mapping, and zone accessory options.
To edit a zone, follow these steps:
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Press 2 to enter Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the zone number, then press ENTER.
Edit Zone Name
6.
Press 1 to edit the selected Zone Name.
You can use words to display a descriptive name for a zone.
NOTE: See Appendix A for editing names.
Edit Zone Properties
Zone properties consist of alarm delay characteristics, heat detector sensitivity, and smoke detector sensitivity.
1.
Do steps 1 through 5 of Section 8.3.1.
2.
Press 2 to edit the properties of the selected zone.
Zone number
Z001
being
programmed
Type: 1-Count____
Heat Sensitivity: [135] Farenheit
Smoke Sensitivity: [LOW ]
Select the sensitivity:
LOW, MEDIUM, or HIGH
NOTE: You only see smoke sensitivity on the IFP-300 if the daytime/nighttime sensitivity is off under the System Options. (See Section 8.6.2).
Otherwise, if you have Daytime/Nighttime Sensitivity on, this will bring up a Smoke Sens Day and Night, 2 separate widgets with sensitivity as
being either low, medium, or high for each.
Alarm Delay Characteristics
The programmed zone type is provided for the user reference only. To modify the zone type, use the HFSS Honeywell Fire Software Suite.
Select the alarm delay characteristics (see Table 8.2 below) by pressing the up or down arrow.
Type of Delay
1
1-Count
2-Count
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Figure 8.2 Edit Zone Properties
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device of any of the
following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is considered the most typical
operation and is the default for all zones.
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order for the zone to
report an alarm. Switches of type manual pull, water flow, Detector Switch, Aux1 and Aux2 are an exception; they will
cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a pre-alarm condition. In a pre-alarm condition,
the touchpad PZT beeps and the annunciator display indicates that a pre-alarm has occurred. If the zone has been
mapped to an output group for the pre-alarm event, the output group will activate. The pre-alarm will not be reported to
the central station.
Description
Table 8.2 Alarm Delay Types
Programming
Detection type also selected
from this screen (see Table 8.2).
Select the temperature that will cause heat
detectors in this zone to go into alarm.
Range: 135°-190° (IDP/SK devices)
135°-150° (SD devices)
97

Advertisement

Table of Contents
loading

Table of Contents