Changing Module Options; 2: Adding A Module; 3: Deleting A Module; 4: View Module List - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

7.
If you wish to edit the module's name, press the ENTER on the modules name. Then press the number keys corresponding to the
character to select each character for the module's name (or press the right arrow to bypass editing the name).
Press the right arrow to move to the next character.
Appendix B
NOTE: See
Default name for the Internal
SLC module
(no customization)
Use up or down arrow key to select
Mode. Press the number until
the character wanted is
shown. Press left/rt arrow

Changing Module Options

Each module has a unique set of options that specifically applies to the functionality of the module being edited.
8.
Use the left and right arrow keys to move between available options.
9.
Option settings are edited by pressing the up or down arrow.
9.2.2 Adding a Module
To add a new hardware module to the system, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Enter the installer code. The panel will automatically go the main menu.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Press 2 to add a module.
5.
From the next screen, select the number that corresponds to choose a module type to add from the <New Module Type> screen.
The screen will display "Adding module [#]..." for a few moments. You will be returned to the <New Module Type> screen where
you can add additional modules if desired.
You must save changes when you exit the Program Menu or the new module will not be added.
NOTE: If you Add a Module that has not been physically connected, the panel will go into trouble after it reinitializes (when you exit the
Program Menu). When the new module is attached, the trouble will correct itself automatically.
9.2.3 Deleting a Module
To delete a module, follow these steps:
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Enter the installer code. The panel will automatically go the main menu.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Select module to be deleted.
5.
Press 3 to delete a module.
6.
A warning screen will display. If you want to proceed with deleting the module, select Yes. To cancel, select No.
9.2.4 View Module List
To view a list of all modules, follow these steps:
1.
Enter the installer code. The panel will automatically go the main menu.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Press 4 to view module list.

9.3 Zone

Through the zone option in the program menu you can edit and view zone points. Selections made here affect all detectors and switches
in the zone. Up to 999 zones can be used in the system.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
for editing name.
Figure 9.1 Edit module Name Programming Screen Example
115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs