Reporting

11.2 SIA - Panels PI Modifier Reporting

Events are sent to the Central Station as a variable length string.
The event format is:
EEZZZZ
Where:
EE
Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1.
The account number is sent using an account block that is separate from the event block
2.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
3.
Event parameter can be either a zone, point or module number.
4.
When reporting by point is enabled, the communicator uses a "pi" event to supersedes the actual point event to report the module the
point is linked to.
5.
Panel ID is not sent in the SIA event parameters.
For Example see Table 11.3:
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander 18
SLC Loop Shorted
Program Begin Panel ID=32
Program Begin Panel ID= 22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-NAC
Fire Trouble-NAC
11.3 SIA – Panel Communicator
(The differences/additional features are underlined).
Events are sent to the Central Station Receiver as a fixed length string.
The event format is:
EEPPMMZZZZ
Where
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1.
The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM) and a
4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case the
field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
"pi" modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
154
Report
Event
Zone/
Point
Zone
Zone
Point
Point
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Point
Zone
Point
Zone
Table 11.3 SIA / Panels - PI Modifier Reporting Examples
Panel
Modul
Zone
ID
e
ZZZZ
n/a
n/a97
15
n/a
n/a
n/a
05
n/a
n/a
01
n/a
123
n/a
33
n/a
203
n/a
11
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
n/a
18
n/a
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
n/a
97
n/a
200
n/a
97
01
n/a
n/a
98
n/a
Nac Circuit 7
n/a
98
n/a
Nac Circuit 7
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
SIA - Panels PI Modifier Reporting
Point
Fields Sent
ZZZZ
EE-ZZ
EE-Z
EE-ZZ /EE-ZZZ
EE-ZZ /EE-ZZZ
EE-ZZ
EE-Z
EE-ZZ
EE-ZZ
EE-ZZ
EE-Z
EE-Z
EE-Z
EE-ZZ /EE-ZZZ
EE-Z
EE-ZZ /EE-Z
EE-ZZZ
SIA Event
Data
FA15
FA5
pi01/FA123
pi11/FA203
ET11
RP0
YT98
YT18
ET44
LB0
LB0
AT0
pi97/FT200
FT1
pi98/FT7 Z=Pt. #
FT400 ZZZ=OPG#

Advertisement

Table of Contents
loading

Table of Contents