Remote Station Applications
Wire the SD500-ARM as shown below.
Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override
trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset. If an
alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current: 15 mA max.
Operating Voltage: 24 VDC nominal
Resistance: 4 KΩ
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Figure 4.51 Polarity Reversal Connection Using the SD500-ARM Module
EOL
Control Panel Installation
Intended for connection to a
polarity reversal circuit of a
Remote Station Receiving
Unit having compatible rating.
to remote
receiving station
61