Honeywell Farenhyt Series Manual page 149

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Receivers Compatible with the Control Panel
Event Description
Voice Aux ECS 4 Alarm Restore
Water flow switch alarm
Water flow switch alarm Restore
Water flow switch trouble
Water flow switch trouble Restore
Zone-based AUX1 switch alarm
Zone-based AUX1 switch alarm restore
Zone-based AUX1 switch trouble
Zone-based AUX1 switch trouble restore
Zone-based AUX2 switch alarm
Zone-based AUX2 switch alarm restore
Zone-based AUX2 switch trouble
Zone-based AUX2 switch trouble restore
Point Events
An unexpected SLC device has been
detected
An unexpected SLC device has been
removed
Auxiliary power disabled
Auxiliary power enabled
Auxiliary power Trouble
Auxiliary power trouble restore
Background Music Switch is Trouble
Background Music Switch is Trouble
Restored
Background Music Switch is Disabled
Background Music Switch is Enabled
CO Detector Trouble
CO Detector Trouble Restore
CO Detector Disabled
CO Detector Enabled
Detector Alarm
Detector Alarm restore
Detector Disabled
Detector Enabled
Detector Trouble
Detector Trouble restore
Detector CO Alarm
Detector CO Alarm Restore
Detector CO Supervisory Alarm
Detector CO Supervisory Alarm Restore
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
SIA Reporting Format
SIA pi Modifier
Module
SIA
Parameter
ID #
Event
(If Any)
Code
s
UH
6
SA
Zone #
SH
Zone #
ST
Zone #
SJ
Zone #
UA
Zone # + 1000
UH
Zone # + 1000
UT
Zone # + 1000
UJ
Zone # + 1000
UA
Zone # + 2000
UH
Zone # + 2000
UT
Zone # + 2000
UJ
Zone # + 2000
For IDP/SK devices, sensors 1–159 are reported as Points 1–159, modules 1–159 are reported as
pi Exp. ID XE
Point #
pi Exp. ID XI
Point #
pi Exp. ID FB
Point #
pi Exp. ID FU
Point #
pi Exp. ID FT
Point #
pi Exp. ID FJ
Point #
pi Exp. ID UT
Point #
pi Exp. ID UJ
Point #
pi Exp. ID UB
Point #
pi Exp. ID UU
Point #
pi Exp. ID GT
Point #
pi Exp. ID GJ
Point #
pi Exp. ID GB
Point #
pi Exp. ID GU
Point #
pi Exp. ID FA
Point #
pi Exp. ID FH
Point #
pi Exp. ID FB
Point #
pi Exp. ID FU
Point #
pi Exp. ID FT
Point #
pi Exp. ID FJ
Point #
pi Exp. ID GA
Point #
pi Exp. ID GH
Point #
pi Exp. ID GS
Point #
pi Exp. ID GR
Point #
Table 11.2 Report Formats Table (Continued)
Contact ID Reporting Format
SIA
Fixed Length
Qualifier Event
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
UHNN006000
3
SANN000ZZZ
1
SHNN000ZZZ
3
STNN000ZZZ
1
SJNN000ZZZ
3
UANN001ZZZ
1
UHNN001ZZZ
3
UTNN001ZZZ
1
UJNN001ZZZ
3
UANN002ZZZ
1
UHNN002ZZZ
3
UTNN002ZZZ
1
UJNN002ZZZ
3
Points 201–359.
XENNXXPPPP
1
XINNXXPPPP
3
FBNNXXPPPP
1
FUNNXXPPPP
3
FTNNXXPPPP
1
FJNNXXPPPP
3
UTNNXXPPPP
1
UJNNXXPPPP
3
UBNNXXPPPP
1
UUNNXXPPPP
3
GTNNXXPPPP
1
GJNNXXPPPP
3
GBNNXXPPPP
1
GUNNXXPPPP
3
FANNXXPPPP
1
FHNNXXPPPP
3
FBNNXXPPPP
1
FUNNXXPPPP
3
FTNNXXPPPP
1
FJNNXXPPPP
3
GANNXXPPPP
1
GHNNXXPPPP
3
GSNNXXPPPP
1
GRNNXXPPPP
3
Reporting
Group #
Contact #
Code
174
00
000
113
00
Zone #
113
00
Zone #
373
00
Zone #
373
00
Zone #
140
01
Zone #
140
01
Zone #
373
01
Zone #
373
01
Zone #
140
02
Zone #
140
02
Zone #
373
02
Zone #
373
02
Zone #
380
Exp. ID
Point #
380
Exp. ID
Point #
571
Exp. ID
Point #
571
Exp. ID
Point #
320
Exp. ID
Point #
320
Exp. ID
Point #
379
Exp. ID
Point #
379
Exp. ID
Point #
580
Exp. ID
Point #
580
Exp. ID
Point #
373
Exp. ID
Point #
373
Exp. ID
Point #
571
Exp. ID
Point #
571
Exp. ID
Point #
110
Exp. ID
Point #
110
Exp. ID
Point #
571
Exp. ID
Point #
571
Exp. ID
Point #
373
Exp. ID
Point #
373
Exp. ID
Point #
162
Exp. ID
Point #
162
Exp. ID
Point #
200
Exp. ID
Point #
200
Exp. ID
Point #
149

Advertisement

Table of Contents
loading

Table of Contents