Control Panel Installation
4.10.1 5815XL Connection to the Panel
Connect the 5815XL to the control panel as shown below. After the 5815XL is connected to the panel, it must be added to the system. This
programming steps are described in Section 8.2.2.

4.11 6815 Installation

The 6815 SLC expander lets you add additional addressable devices. The maximum number of SLC devices per panel is 300. The number of
6815 modules is limited by the maximum number of SBUS devices.
NOTE: 6815 will support IDP, SK, and SWIFT wireless devices.
To install the 6815:
1.
Make sure power is off at the panel.
2.
Mount the 6815 in the IFP-300 cabinet, the RPS-1000 cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under
the control panel board assembly and secure with screws provided with the 6815. For additional information, see the RPS-1000
Installation Manual (P/N 151153) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 6815 to the control panel. (See Section 4.11.1.)
4.
Use onboard DIP switches to select an SBUS ID#. (See Section 4.15.1.)
5.
Add the 6815 module to the system through programming. JumpStart will add the module automatically (see Section 7.1). You can also
add it manually (see Section 8.2.2). Select a name, if desired (See "Naming Modules" on page 76.).
46
5815XL
SLC Out
SLC In
SBUS
-
A B
+
SC-
S+
SC-
S+
Figure 4.28 5815XL Connection to the IFP-300
IFP-300
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
supervised,
power-limited,
Class B
5815XL
SLC Out
SLC In
SBUS
-
+
A B
SC-
SC-
S+
S+
6815 Installation

Advertisement