System Operation
Conditions Required for an Interlock Release Alarm Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated addressable detectors. When
these conditions are met, the "Interlock Release Alarm" and "Detector Alarm" outputs will activate, and the "Interlock Release Alert" out-
puts will deactivate.
Inputs
1st Addressable
Detector
2nd Addressable
Detector
Manual Release
Station
Interlock/Pressure
Switch
Normal
CAUTION: DETECTOR SPACING
!
DETECTORS MUST BE INSTALLED AT 0.7 TIMES THE LINEAR SPACING AS DESCRIBED IN NFPA 72

9.7 Smoke Alarm Verification

Figure 9.7 illustrates how the Smoke Alarm Verification cycle operates.
reset period
12 seconds
If there is no alarm indication during the confirmation period, the system will return to normal operation.

9.8 Function Keys

The function keys on the IFP-300 have multiple features. Their macro key functionality can simplify the disabling, activating, or inhibiting
points or groups respectively. They can also be used as a status type activation event and for activating Map Inhibit. Each F-Key macro can
hold 50 events.
To Access the F-Key Recording Menu:
1.
From the Idle screen, press and hold the F-Key for 5 seconds.
2.
Enter a PIN with F-Key macro recording privileges, if prompted.
9.8.1 Recording an F-Key Macro
1.
Access the F-Key Recording menu and select the 'Start FKEY Recording' option.
2.
The panel will return to the Idle screen. Notice the 4th line on the display now alternates with "F# Key Recording", where # is the
number of the F-Key being recorded.
3.
Any Disabling or Activating of points, output groups, or templates from the site at this point will be programmed into the macro. Do
this by going to any annunciator within the site and entering Main Menu > Point Functions and use Disable/Enable Point or use I/O
Point Control to: disable output groups or individual points, or activate individual points.
4.
Once you are finished with disabling or activating points/output groups, enter the F-Key Recording Menu again and select the 'End
FKEY Recording' option.
5.
The panel will return to the Idle screen.
9.8.2 Aborting an F-Key Macro Recording Session
1.
After an F-Key macro recording session has been started, the session can be canceled at any time by accessing the F-Key Recording
menu and selecting 'Abort FKEY Recording' option.
2.
The panel will return to the Idle screen.
132
X
X
X
X
X
Interlock
Release
Interlock Release Alert and Detector Alarm
Alert
Table 9.6 Double Interlock Zone Operation
restart period
16 seconds
Figure 9.7 Smoke Verification Cycle
Output Results
X
X
X
X
X
X
X
X
confirmation period
60-250 seconds
(programmable)
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Smoke Alarm Verification
X
X
X
X
X
X
X
X
X
Interlock Release Alert and
Detector Alarm
X
X
X
X
X
X
X
X
X
X