4.9.2 RA-2000 Connection to the Panel
Connect the RA-2000 to the panel as shown below.
4.10 5815XL Installation
The 5815XL SLC expander lets you add additional addressable SD devices. The maximum number of SD SLC devices per panel is 254. The
number of 5815XL modules is limited by the maximum number of SBUS devices.
NOTE: 5815XL will only support SD protocol devices on this panel.
To install the 5815XL:
1.
Make sure power is off at the panel.
2.
Mount the 5815XL in the IFP-300 cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control panel
board assembly and secure with screws provided with the 5815XL. For additional information see the RPS-1000 Installation Manual
(P/N 151153) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 5815XL to the control panel. (See Section 4.10.1.)
4.
Use onboard DIP switches to select an SBUS ID#. (See Section 4.15.1.)
5.
Add the 5815XL module to the system through programming. JumpStart will add the module automatically (see Section 7.1). You can
also add it manually (see Section 8.2.2). Select a name, if desired (See "Naming Modules" on page 76.).
You are now ready to connect SLC devices to the 5815XL. Refer to the SLC Wiring Manual for compatible devices.
Figure 4.27 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
supervised,
power-limited
Class B
Figure 4.26 RA-2000 Connection to the Panel
+
A
B
S B U S
Figure 4.27 5815XL Board