Programming
8.5.2 Point Programming for a 6815 Module
To program for points on a 6815 module, follow these steps:
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then, press ENTER.
5.
Select S for sensor or M for module. (IDP or SK devices only)
6.
Enter the number of the point you want to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to the column heading, "Type Selection" in the table below for a
list of choices.
Type
Function
Selection
UNUSED
DETECTOR
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
2-WIRE SMOKE
SUP DET
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO SMOKE
CO ALRM /
DETECTOR
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
FIRE SUPR
W-DETECTOR PHOTO
ACCLIMATE (IDP)
HEAT
PHOTO-HEAT
(SK)
W-SUP DET
Same as
W-Detector
106
Latching Option
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Acclimate photoelectric detector.
High temperature heat detector.
Photoelectric detector with heat sensor.
Beam smoke detector.
2-wire smoke detector.
Latching
Use this option when you want a detector to indicate a supervisory alarm.
Non Latching
No Accessory Base, Sounder base, Relay Base, or Intelligent Sounder base.
Bases can be set for Single station or Multi station, Silence or Non-Silence, Latching or
non-latching. Intelligent sounder bases can have volume set for high or low.
Latching
Supervisory switches can be latching or non-latching.
Non Latching
Latching
Wireless photoelectric detectors
Non Latching
Wireless acclimate photoelectric detector
Wireless heat detector
Latching
Wireless photoelectric detectors
Non Latching
Table 8.7 Programming Options for 6815 Modules