10: Reset Alarms; 11: Check Detector Sensitivity Through Point Status - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

System Operation
NOTE: This system has the ability to silence control panels across the ECS network.
NOTE: For ECS systems, pressing silence at an LOC will only silence the system in control. See Section 9.4.1.
9.3.10 Reset Alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch has been installed, activating the switch will
reset alarms. If you are already using system menus when you press RESET, you will not need to enter your code or rotate the key.
NOTE: Multi-Site displays do not allow for resetting multiple sites. To reset a site, enter a Multi-Site Installer access password, select a site
from the list of Sites, and then press Silence or Reset button to continue. This option will occur whether the Network was programmed No/Yes
for "Silence-Reset Across Sites". Also, this option allows the user to select Reset Fire System and Reset Emergency Communication System
whether or not the panel has ECS. If the user selects No, the non-ECS panel will do a fire reset within the site and no other sites will be affected.
NOTE: For ECS Systems, pressing reset at an LOC will prompt the user for which system they want to reset. See Section 9.4.1.
Reset Communicator
This options allows the user to reset the communicator. The LCD will display:
"Resetting Communicator... Please Wait"
You will be returned to the Main Menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the follow-
ing are active:
Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
ECS Alarm
ECS Supervisory
9.3.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL
MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the Central Station receives a detector trouble report ("373" and the zone or point for Contact ID for-
mat; "FT" and the zone or point in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
124
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Basic Operation