Recording Custom Messages; 1: Recording Messages 1-15 Using Aux Audio Input - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Recording Custom Messages

10.8 Recording Custom Messages
The ECS-VCM or ECS-EMG keypad comes with 15 recordable message slots. Messages 1-15 can be recorded from the microphone, Aux
Input, or by using the Message Manager utility of HFSS. All messages can be a maximum of one minute.
When in the record mode the ECS-VCM or ECS-EMG switches will function as follows:
Select Keys
While in the Local Record mode, select keys 1-15 will be used to reference message slots 1-15. The associated green Select key will indicate
that a message is currently programmed in the corresponding slot. When there is no message recorded (or the message is erased), the associ-
ated green Select key LED will be off. While recording a particular message, the red Select key will turn on until recording is completed. The
Select key 1-15 will be used to playback a recorded message or to select a message slot to record to or erase.
When in the Local Record mode, the ECS-VCM or ECS-EMG LEDs will function as follows:
Switch LED
Select key 1-15 Green LED
Select key 1-15 Red LED
Select key 1-15 Green/Red LED
Select key 1-15 Red LED
10.8.1 Recording Messages 1-15 Using Aux Audio Input
Recording messages from the Aux Audio Input enables you to load customized, pre-recorded messages into an ECS message location.
Follow these steps to input user message using Aux Audio Input.
1.
Wire a speaker cable with 1/8" mini plug to Aux AUDIO GND and IN terminals. See Figure 10.5 below.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
READY
ALL CALL
TO TALK
1-15
Key
ECS Message Key 1
ECS Message Key 3
ECS Message Key 8
Select Keys 1-15
Active LED Status
On
On
Off/Off
Flashing
Table 10.1 LED Functions During Programming
NON-ACTIVE
ECS CONTROL
CALL
Function
Select message slot to record
Start and stop recording from Aux Audio Input
Erase user message 1-15
Message storage lot 1-15
Message is currently programmed in this slot
Message recording is in progress
Message slot is empty
Message is being played back or message is selected for recording
Emergency Communication System Operation
ECS Message Key 1
ECS Message Key 3
ECS Message Key 8
Action
141