Honeywell Farenhyt Series Manual page 109

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Point
.
Choices
Enter Point
Select Type
Select Zone/Group
Edit Name
1
Only applicable to RPS-1000
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Function Selections
Type Selections
for each Type
UNUSED
B NOTIF
NOTIF OUTPUT
CONTROL CIRCUIT
A NOTIF
Same as B NOTIF
AUX_PWR
CONSTANT
AUX RESET
AUX DOOR
AUX SYNC
1
B SWITCH
MANUAL PULL
WATERFLOW
SUPERVISORY
TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
ECS TAMPER
ECS SUPERVISORY
1
A SWITCH
Same as B SWITCH
1
B DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
1
A DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
Table 8.8 Menu Choices for Internal/External Power Module
Comments
User also has Supervised/Unsupervised option
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Power Sync
Refer to comments column of Table 8.6 and Table 8.7 for
description of these options. Latch or Non-latching feature only
appears for WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM AUX1,
SYSTEM AUX2, ECS INPUT, ECS TAMPER, and ECS
SUPERVISORY.
User also has ECS Event Number 1-8 option for ECS INPUT.
Only available when an ECS-VCM or ECS-NVCM is installed in
the system.
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire CO
Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Group or Zone selection will appear depending on the type
selected.
See Appendix A.
Programming
109