Honeywell Farenhyt Series Manual page 42

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Control Panel Installation
Flush Mounting Steps
1.
Cut a hole in the sheet rock to the following dimensions: 8-1/4" W x 6-5/8"H. If an electrical box is used, the box must be 1-3/8" back
from face of wall to accommodate the annunciator.
2.
Remove knockout holes as needed for wires.
3.
Fit the annunciator backbox into the hole and stabilize with mounting wires. Angle the mounting wires into the first hole past the sheet
rock. Secure the wires behind the screws as shown in Figure 4.20. When all four wires are in place, the backbox should fit snugly into
the hole in the sheetrock.
4.
After the annunciator wiring to the panel has been completed (refer to Figure 4.11), replace the electronic assembly in the back box.
Place the bezel over the back box and tighten the set screws on the bezel.
Surface Mounting
The RA-1000 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. Trim Ring Kit
5860TR/Gis available for use when surface mounting.
1.
Drill holes in the surface to match the screw holes on the backbox. Refer to Figure 4.19 for locations.
2.
Fit the trim ring over the backbox.
3.
Attach the backbox to the wall using screws provided.
4.
Wire the annunciator to the FACP as shown below.
5.
Replace the electronic assembly in the backbox. Place the bezel over the backbox and tighten the set screws on the bezel. Refer to
Figure 4.19 for location of set screws.
42
Attach second set of wires to top of backbox.
Secure wires behind screw.
Insert wires at an angle into the first holes past sheetrock.
Figure 4.20 Flush Mounting the Backbox
supervised,
power-limited
Class B
Figure 4.21 RA-1000 Connection to the Panel
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
RA-1000 Remote Annunciator Installation