Event History

2.
Press 1 for System Test.
3.
Press 1 to select Fire Drill.
4.
Press ENTER to begin the drill. To end the drill, press any key.
To conduct a fire drill from a remote fire drill switch: Activate the switch to begin the drill; de-activate the switch to end the drill. Measure
battery voltage while the Notification Appliances are sounding. Replace any battery with terminal voltage less then 85% of rating. Reapply
AC power and press RESET. Return all switches to their normal outward positions. Notify fire department, central station and/or building
personnel that the test is complete.
12.3 Event History
The Event History can be useful for tracking or recalling a trouble condition.
To view the Event History, do the following.
1.
Login to the panel.
2.
Press 3 to select Event History.
3.
Press the up or down arrow key to view events in the history buffer.

12.4 Built-in Troubleshooting and Testing Tools

The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and troubleshooting
points and SLC devices.
12.4.1 SLC Device Locater
SLC device locater can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1.
Select 2 for Point Functions from the Main Menu.
2.
Select 4 for SLC Single Device Locater.
A message similar to the one shown below will display.
3.
Press ENTER to accept, or left arrow to Exit.
If left arrow is chosen you will exit back to the Point Function Menu.
If ENTER is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6.
Press left arrow key to exit the SLC Device Locater.
NOTE: Once you exit, the system will resume normal operation.
12.4.2 SLC Multiple Device Locater
This feature is the same as SLC Single Device Locater, except you can locate up to 8 devices on a single search.
Follow these instructions to locate multiple SLC devices:
1.
Select 2 for Point Functions from the Main Menu.
2.
Select 5 for SLC Multiple Device Locater.
A message similar to the one shown below will display.
3.
Press ENTER to accept, or left arrow to Exit.
If left arrow is chosen you will exit back to the Point Function menu.
If ENTER is chosen the system will cease normal operation leaving the premise unprotected.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
The system will be shut down during SLC
device locating.
= Back
Figure 12.1 Shut Down Warning
The system will be shut down during SLC
device locating.
= Back
Figure 12.2 Shut Down Warning
[Enter] to Accept
[Enter] to Accept
Testing and Troubleshooting