2: Recording Messages 1-15 Using The Microphone - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Emergency Communication System Operation
2.
Plug the mini plug into the Line Out/Headphone jack on a PC or Laptop.
terminal block connection
on ECS-VCM/ECS-NVCM
3.
Enter programming mode at the main control panel.
4.
Select option 8 for System Options.
5.
Select option 1 VCM Maintenance.
6.
Select option 2 Local Recording.
NOTE: The keypad will light the green Select Key LED for message slots that are occupied. If a message is already stored in the desired slot,
then you must erase the message first.
7.
Select the amplifier and circuit for the audio to play through during programming. A user would generally pick the audio circuit that is
in closest proximity to them.
8.
Press ECS Message key 1 to enter the message slot selection mode. Then, press the Select key 1-15 that corresponds to the message slot
to which you want to record. The associated Select key red LED will begin flashing, indicating that the message slot is ready for
recording.
9.
Simultaneously press ECS Message key 3 and start playing the audio source on the PC or laptop.
10. When the audio file from the PC is finished playing, press ECS Message key 3 again to stop the recording. The Select key green LED
will turn on.
11. To playback the recorded message, press the Select key 1-15 that was just recorded.
Recording with Aux Audio Input Example
The user wants to record into memory slot 2 via the Aux Audio Input channel.
Upon entering the Local Recording mode via the keypad menu, the keypad will light the green LEDs of Select keys 1-15 for each occupied
message slot.
If a message already exists in message slot 2, it must first be erased. Press ECS Message key 8, then press Select key 2, (refer to
Section 10.8.3). When the message has been erased, the Select key 2's green LED will turn off.
To record a message, press ECS Message key 1, then press Select key 2 (this will use message slot 2 for the recording). Select key 2's red
LED will begin flashing.
Press ECS Message key 3, while simultaneously pressing play on the PC to start recording the Aux Audio Input. When the PC message is
done, press ECS Message key 3 to stop recording. Select key 2's red LED will stay on until processing is completed. Select key 2's green
LED comes on after the recording is completed.
Pressing Select key 2 will start a playback of the recorded message.
10.8.2 Recording Messages 1-15 Using the Microphone
Messages can be recorded into the ECS system by using the onboard microphone.
Follow these steps to use the microphone to record your message:
1.
Enter programming mode at main control panel.
2.
Select option 8 Voice Options.
3.
Select 1 for VCM Maintenance.
4.
Select option 2 Local Recording.
142
Figure 10.5 AUX Audio Connection for Recording
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Recording Custom Messages
plug in speaker cable
to Audio/Line Out

Advertisement

Table of Contents
loading

Table of Contents