JumpStart Auto-Programming

8.6.8 SLC Family
The IFP-300supports SD, Intelligent Device Protocol (IDP), or SK Series SLC devices. You must configure the IFP-300 to accept the proto-
col of the devices you are installing. You cannot mix SLC devices of different protocols.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 8 for SLC Family.
5.
Press UP arrow to select the desired SLC device type.
6.
Press ENTER to accept the displayed SLC device type.
NOTE: When you change the SLC type from one protocol to another, the following message will appear.
When changing SLC family from IDP or SK to SD will remove all external 6815 modules. When changing from SD to IDP or SK SLC fam-
ily will remove all 5815XL modules on the system.
8.7 JumpStart Auto-Programming
NOTE: JumpStart Auto-Programming is used to auto learn the system hardware after devices have been added or removed from the system.
Hardware devices which remain the same between repeat JumpStart will retain any customized text or options associated with the device. It is
best to carefully consider the Network ID setting for each panel before the first JumpStart Auto-Programming is performed. Once this is done,
the panel must be defaulted back to factory defaults if the network ID settings need to change.
To run JumpStart Auto-Programming, do the following steps.
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Select 6 for JumpStart.
4.
Press ENTER to accept the Warning screen.
5.
Follow the remaining on screen instructions
6.
Press ENTER to confirm. See Section 7.1.3.

8.8 Restore Defaults

This option allows you to restore the panel back to factory defaults. All programming will be lost.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 7 for Restore Defaults.
4.
Press the up or down arrow key to select YES or NO from the warning screen. Then press ENTER.

8.9 Voice Options

Through this programming menu you can modify the messages programmed into an NVCM/VCM. You can also modify other voice settings.
8.9.1 VCM Maintenance
The VCM Maintenance menu is used to program custom messages into the NVCM/VCM. Messages can be recorded locally using the
microphone.
1.
Select 7 for Panel Programming.
2.
Select 8 for Voice Options.
3.
Select 1 for VCM Maintenance.
8.9.2 Voice Settings
1.
Select 7 for Panel Programming.
2.
Select 8 for Voice Options.
3.
Select 2 for Voice Settings.
Enable Dual Channel System
This option allows you to select whether the dual channel is enabled in the System. For dual channel capabilities, the system must only con-
tain dual channel voice hardware.
To enable the System as a dual channel, press the up or down arrow key to select YES or NO. Then, press ENTER.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Setting the SLC family will set all
SLC point to UNUSED
Back
Figure 8.14 SLC Family Change
[Enter] to Accept