Advertisement

System Options
Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow switch. The delay is system-
wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown below will display.
5.
Enter the number of seconds (0 to 90) to delay a water flow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
To set the alarm verification, do the following.
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow key or ENTER to make your selection and move the cursor to the next programming option.
AC Report Delay
NOTE: You must select 1-3 hours for AC Delay Time in UL Central Station and UL Remote Signaling installations.
You can adjust the number of hours before a Low AC Report will be sent to the Central Station.
8.
Enter the number of hours (0-30) before a low AC Report will be sent to the Central Station, then press ENTER.
Change AC Line Frequency
The panel's AC line frequency is selectable for 50, 60 Hz, or Internal. The AC Frequency feature dictates how the control panel will calcu-
late time based on the AC line frequency used in the installation site. The "Internal" option can be used in areas where the AC line frequency
is not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power
source and either 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz selection.
To change the AC line frequency, continue programming from step 9 above:
9.
Select 50, 60 or Internal, by pressing the up or down arrow, then press ENTER.
Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then press
ENTER.
Auto-Resound (4 or 24 hours)
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto-
matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices.
8.6.5 Miscellaneous Options
Through this programming option, you can turn on or off the strobe synchronization during silence, and display status at Idle (auto display
event).
To edit the Miscellaneous Options, do the following.
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Miscellaneous Options.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
delay in seconds before
waterflow alarm occurs (00-90)
Water Flow Delay: 01s Alarm Verify: 060s
AC Report Delay: 06h AC-Frequency: 60Hz
Clock Format: AMPM
<Water Flow Delay (0-90s)>
Figure 8.13 Water Flow Delay Programming Screen
Auto-Resound: 24Hr
Programming
115