Control Panel Installation
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as
possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 4.3 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire
through ferrite shield beads or by wrapping it around a ferrite toroid.
0.25" spacing must be
maintained between each of
these circuit types, as well as
between power-limited and non-
power-limited circuits.
0.25" spacing must be
maintained between each of
these circuit types, as well as
between power-limited and non-
power-limited circuits.
32
AC power
SLC
battery
Figure 4.3 Wire Routing Example for IFP-300
AC power
SLC
VBUS
battery
Figure 4.4 Wire Routing Example for IFP-300ECS
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
NAC/aux power circuits
relay circuits
SBUS
phone lines
battery
NAC/aux power circuits
relay circuits
SBUS
phone lines
relay circuit
network connections
battery
Wiring Specifications