Programming Overview
7.2.3 Event Mapping
There are 11 types of Zone events, 14 types of Panel events, and 40 types of Site events that can be mapped. For each event type, you can
activate the output groups with specific output patterns. Mapping examples are shown in Figures 7.4, 7.5, and 7.6.
System
Fire
Emergency
Advisory
1
Temporal 4 coding cannot not be used for NAC circuits on CO Supervisory events.
80
Zone
Manual Pull Alarm
Water Flow Alarm
Detector Alarm
(heat or smoke detectors)
Zone Aux 1 Alarm
Zone Aux 2 Alarm
Interlock Alert
Interlock Release
Pre-Alarm
Fire Supervisory
Status Point
CO Alarm
1
CO Supervisory
Trouble
Status Point Active
Zone 1:
manual pull alarm
This example shows Zone 1 manual pull alarm event mapped to:
• Group 1 using constant output.
• Group 5 using ANSI 3.41 output pattern.
Figure 7.4 Example of Zone Events Mapped to Output Groups and Patterns
Panel
System Aux 1 Alarm
System Aux 2 Alarm
SBUS Expander Trouble
SBUS Class A Trouble
SLC Loop Trouble
AC Loss Trouble
Battery Trouble
Ground Fault Trouble
Phone Line Trouble
Reporting Account Trouble
Printer Trouble
Aux Power Trouble
System Switch Trouble
Output Group Trouble
Table 7.2 Event Mapping
pattern 00
constant
pattern 02
ANSI 3.41
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Mapping Overview
Site
Fire Drill
General Fire Alarm
General Fire Supervisory
General Fire Pre-Alarm
LOC ECS 1-8 Alarm
General ECS Alarm
General ECS Supervisory
Point ECS 1-8 Alarm
General Trouble
Site Silenced
Voice Aux In 1-8 Alarm
F1 Key Active
F2 Key Active
F3 Key Active
F4 Key Active
Voice Aux in 1-2
System Mic Active
Background Music
group 1
group 2
group 3
group 4
group 5
group 6
through
group 250