Honeywell Farenhyt Series Manual page 129

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Panel Operating Modes
Operating
Occurs When
Mode
Supervisory
The system detects a
supervisory condition.
A Supervisory with a
CO detector.
Trouble
A system trouble
condition occurs.
A trouble condition
with a CO detector
Pre-alarm
A single detector trips
in a 2-Count zone.
(2-Count means two
detectors must trip
before an alarm is
reported.)
Reset
The RESET button is
pressed followed by a
valid code, if
necessary.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
System Behavior
The system will report events to the central station.
The onboard annunciator sounds a loud, pulsing beep
to distinguish supervisory signals. For fire supervisory
signals, the sequence is two seconds on, two seconds
off. For ECS supervisory signals, the sequence is two
seconds on, three seconds off.
The SUPERVISORY LED will turn on.
The LCD displays a screen similar to this one.
Site 1
FIRE: SUPERVISORY
<Press for status>
Pressing the down arrow to display the location
macro, date/time stamp, and site/panel, if applicable.
Site 1
CO: SUPERVISORY
<Press for status>
Press the down arrow to view the type and location of
the Supervisory event. The message will alternate
with the time/date display.
The system will report events to the central station.
The onboard annunciator sounds a loud, pulsing beep
in the sequence 0.75 second on, eight seconds off.
The SYSTEM TROUBLE LED will turn on.
The LCD displays a screen similar to this one.
Site 1
FIRE: TROUBLE
<Press for status>
Press the down arrow to display the location macro,
date/time stamp, and site/panel, if applicable.
Site 1
CO: TROUBLE
<Press for status>
Press the down arrow to view the type and location of
the Trouble event. The message will alternate with the
time/date display.
The touchpad piezo beeps.
The LCD displays a screen similar to this one.
Site 1
FIRE: PREALARM
<Press for status>
Press the down arrow to display the location macro,
date/time stamp, and site/panel, if applicable.
All LEDs are on briefly then the LCD displays "RESET
IN PROGRESS". If the reset process completes
normally, the date and time normal mode screen
displays.
Table 9.4 Panel Operating Modes (Continued)
In This Mode You Can
Press the down arrow to view the fire supervisory
condition. A screen similar to this one displays.
Site 1 Panel 1
FIRE SUPERVISORY: Supervisory Sw
SBUS 97 MODULE 3
08/03/21 01:45:52PM
Press SILENCE and enter an Access Code (or activate
the key) to silence the annunciator.
Once the supervisory condition has been corrected, the
system will restore automatically.
Press down arrow to view the fire trouble. A screen
similar to this one displays.
Site 1 Panel 1
FIRE TROUBLE: Supervisory Sw
SBUS 97 MODULE 32
08/03/21 01:45:52PM
Press SILENCE to silence the annunciator.
Once the trouble condition has been fixed, the system
will restore itself automatically.
Press down arrow to view the Prealarm. A screen similar
to this one displays.
Site 1 Panel 2
FIRE PREALARM: Det-Photo
SBUS 97 MODULE 33
08/03/21 01:45:52PM 1 of 1
All system operations are available in this mode.
Menus are not available during the reset process.
System Operation
129