Section 2: Agency Listings, Approvals, and Requirements

2.1 Federal Communications Commission (FCC)

The following information must be provided to the telephone company before the IFP-300 can be connected to the phone lines:
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a
label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68
rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this prod-
uct. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected
to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the number of devices
is limited. The REN number is embedded in the FCC registration number as 10A.
If the IFP-300 causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinuance
of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equip-
ment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain unin-
terrupted service.
If trouble is experienced with the IFP-300, for repair or warranty information, please contact Honeywell customer service at 800.328.0103 or
www.farehnyt.com. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the
IFP-300 until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs. You may contact the
state public utility commission, public service commission or corporation commission for information.
Since the IFP-300 is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you
have questions about the installation, contact your telephone company or a qualified installer.
CAUTION: INSTALLATION AND TEST
!
TO ENSURE PROPER OPERATION, THIS EQUIPMENT MUST BE INSTALLED ACCORDING TO THE ENCLOSED
INSTALLATION INSTRUCTIONS. TO VERIFY THAT THE EQUIPMENT IS OPERATING PROPERLY AND CAN
SUCCESSFULLY REPORT AN ALARM, THIS EQUIPMENT MUST BE TESTED IMMEDIATELY AFTER INSTALLATION,
AND PERIODICALLY THEREAFTER, ACCORDING TO THE ENCLOSED TEST INSTRUCTIONS.
CAUTION: LINE IN USE
!
IN ORDER FOR "ALARM DIALING EQUIPMENT" TO BE ABLE TO SEIZE THE PHONE LINE TO REPORT AN ALARM OR
OTHER EVENT WHEN OTHER CUSTOMER EQUIPMENT (TELEPHONE, ANSWERING SYSTEM, COMPUTER MODEM,
ETC.) CONNECTED TO THE SAME LINE IS IN USE, "ALARM DIALING EQUIPMENT" MUST BE CONNECTED TO A
PROPERLY INSTALLED RJ31X JACK. THE RJ31X JACK MUST BE CONNECTED IN SERIES WITH, AND AHEAD OF, ALL
OTHER EQUIPMENT ATTACHED TO THE SAME PHONE LINE. SERIES INSTALLATION OF AN RJ31X JACK IS DEPICTED
IN THE FIGURE BELOW. IF YOU HAVE ANY QUESTIONS CONCERNING THESE INSTRUCTIONS, CONSULT YOUR
TELEPHONE COMPANY OR A QUALIFIED INSTALLER ABOUT INSTALLING THE NECESSARY JACK AND ALARM
DIALING EQUIPMENT.

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for addi-
tional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 9.6 for information on releasing operations.
1.
All field wiring must be installed in accordance with the NFPA 70 National Electric Code.
2.
Use addressable smoke detectors specified in the SLC Wiring Manual (P/N: LS10179-000FH-E and/or the conventional detectors listed
in the Device Compatibility Document (P/N: LS10167-003FH-E).
3.
Use UL listed notification appliances compatible with the IFP-300 from those specified in the Device Compatibility Document (P/N:
LS10167-003FH-E).
4.
A full system checkout must be performed any time the panel is programmed.
14
Manufacturer:
Model Number:
FCC registration number:
Ringer equivalence:
Type of jack:
Facility Interface Codes:
Service Order Code:
Honeywell
IFP-300 and IFP-300ECS
US: HS9AL10A2100
1.0A
RJ31X
Loop Start:
02LS2
9.0F
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022