This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, espe-
cially if you are installing an IFP-300 panel for the first time.

3.1 Inventory

When an IFP-300 shipment is received, check that all the parts have been included in the shipment. The shipment consist of one of each of
the following:
main circuit board with display
backbox with door.
plastic bag containing two keys, screws, cables, and ten 4.7k ohm end-of-line resistors.
manual

3.2 Environmental Specifications

It is important to protect the IFP-300 control panel from water. To prevent water damage, the following conditions should be followed when
you install the units:
Mount indoors in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the IFP-300 control panel, the unit should be mounted where it will NOT be exposed to temperatures
outside the range of 32°F-120°F (0°C-49°C) or humidity outside the range of 10%-93% at 86°F (30°C) non-condensing.

3.3 Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that
you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any
questions about software and the appropriate version for a specific application. Software updates can be found at www.farenhyt.com

3.4 Electrical Specifications

Table 3.1 lists the terminal block on the IFP-300 and a description of the each individual terminal and their respective electrical rating.
Terminal No.
Group
Terminal Block 1
TELCO 1
PHONE 1
TELCO 2
PHONE 2
Terminal Block 2
SLC IN
SLC OUT
SLC PROG
Terminal Block 3
SBUS Out
Terminal Block 4
BATTERY
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022

Section 3: Prerequisites for Installation

Label
Description
Individual
RING
Phone Line 1 Telco Ring
TIP
Phone Line 1 Telco Tip
RING
Phone Line 1 Phone Ring
TIP
Phone Line 1 Phone Tip
RING
Phone Line 2 Telco Ring
TIP
Phone Line 2 Telco Tip
RING
Phone Line 2 Phone Ring
TIP
Phone Line 2 Phone Tip
Used for Class A installations
+
SLC terminals
+
Used for programming SLC
Detectors
+
B
SBUS Communication
A
+
SBUS Power
+
To Positive battery terminal
To Negative battery terminal
Table 3.1 Terminal Descriptions and Electrical Specifications
Rating
Voltage
32 VDC
150 mA
32 VDC
150 mA
32 VDC
150 mA
5 VDC
100 mA
24 VDC
1.0 A
24 VDC
Up to 35 Ah (See Section 4.5 for details.)
Current
17