Sync Network Options - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Network Management
• Fire Alarm
• Fire System Aux 1
• Fire System Aux 2
• Fire Zone Aux 1
• Fire Zone Aux 2
• Fire Prealarm
• Emergency Communication 1
• Emergency Communication 2
• Emergency Communication 3
• Emergency Communication 4
• Emergency Communication 5
• Emergency Communication 6
• Emergency Communication 7
• Emergency Communication 8
• Fire Supervisory
• System Alert 1-5
• Trouble
• Fire Interlock Release
• Fire Interlock Alert
• Custom Emergency Comm
• Emergency Supervisory
• CO Alarm
• CO Supervisory
7.
Select whether a Message or Tone Only should be played. If Message is selected, choose the desired message for the command.
8.
Select the tone to be played between messages. (High-Lo, ANSI Whoop, Cont. Whoop, ANSI, March Code, California, Steady, Alert
Tone, or No Tones).
NOTE: 520Hz tones are available when using the ECS-VCM, ECS-NVCM, ECS-INT50W, or ECS-DUAL50W amplifiers. These include ANSI
520, Temp 4 520, Steady 520. See the Device Compatibility Document for a list of compatible speakers.
9.
Select how many times you wish the message to repeat. (None, 1 - 14, or Continuous).
10. Select the initial delay time (0, 3, 4, 8, 12, 16, 20, 24, 28).
11. Select the inter message delay time (4 to 32 seconds, in 4 second increments).
12. Select Y or N to allow message to continue to play after Mic release.
13. Select Y or N to allow message to restart on a new activation.

6.4 Sync Network Options

If after making changes to network programming, the distribution of network options fail, the system will report a trouble of network options
out of sync. Use this menu to redistribute changed options to the rest of the network. The user will be required to choose a panel to source the
options from. Scroll down through the informational message and press ENTER to view the Select Source screen.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming Menu.
3.
Select 8 for Sync Network Options.
4.
Select from which panel to source the options.
NOTE: If you try to sync with the network and an incompatible panel is found, an error message will display.
74
last time the date and time
were updated on panel
Select Source Last Modified Chk sum
01 = Panel 1 07/28/21 12:20 0F8B
02= Panel 2 07/30/21 09:45 0F8A
03= Panel 3 07/31/21 09:46 0F8A
Figure 6.2 Sync Network Options
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Sync Network Options
If two panels have the same
chk sum, the network options
are in sync.