1: Point Programming For A 5815Xl Module - Honeywell Farenhyt Series Manual

Addressable fire alarm control panel
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Point
Choices
Type Selections
ECS-VCM,
UNUSED
ECS-NVCM,
SWITCH
ECS-RVM
8.5.1 Point Programming for a 5815XL Module
To program for points on an 5815XL module, follow these steps:
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then, press ENTER.
5.
Enter the number of the point you want to edit, then press ENTER.
6.
Select the type of device by pressing the up or down arrow key. Refer to Table 8.6 under the column heading "Type Selection" for a list
of choices.
Type
Selection
UNUSED
DETECTOR
PHOTO
ION
HEAT
PHOTO DUCT
ION DUCT
2-WIRE SMOKE
SUP DET
PHOTO
ION
HEAT
PHOTO DUCT
ION DUCT
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Function Selections for
each Type
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
VOICE AUX STATUS 1-2
VOICE AUX ECS 1-4
Background Music
ECS INPUT
ECS TAMPER
ECS SUPERVISORY
Table 8.5 Point Programming Options
Function
Latching Option
Latching
Non Latching
Table 8.6 Programming Options for 5815XL Modules
Refer to comments column of Table 8.7 on page 106 for description of
these options.
Latch or Non-latching feature only appears for WATERFLOW, FIRE
SUPERVISORY, FIRE TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, ECS INPUT, ECS TAMPER, and ECS
SUPERVISORY.
User also has ECS Event Number 1-8 option for ECS INPUT.
Only available when an ECS-VCM or ECS-NVCM is installed in the
system.
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Duct Ion detector.
2-wire smoke detector.
Use this option when you want a detector to indicate a supervisory alarm.
Comments
Comments
Programming
103

Advertisement

Table of Contents
loading

Table of Contents