This section of the manual is to give you an overview of the programming process. Please read this section of the manual carefully, espe-
cially if you are programming the control panel for the first time.
The JumpStart Auto-programming feature automates many programming tasks and selects default options for the system. You will run
JumpStart at least once when you are installing the system. See Section 7.1 for details. After you run JumpStart, you may need to do some
additional programming depending on your installation. Section 8 of this manual covers manual programmable options in detail.
Programming the panel can be thought of as a four part process. You must program:
Network options. This affects how all panels in the network work together. (see Section 6 for details).
System options. These are options that affect general operation of the panel (see Section 8.6 for details).
Options for input points and zones. These are primarily options that control detection behavior of devices (see Sections 8.3 and 8.5 for
details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping output circuits to output
groups (see Section 8.4 for details).

7.1 JumpStart Auto-programming

The JumpStart Auto-programming feature allows for faster system setup. When you run JumpStart Auto-programming, the panel searches
for expanders and SLC devices not currently in the system. The new devices are added in their default configuration. At the end of Jump-
Start, you can choose to not accept the new devices and go back to the previous configuration. JumpStart saves the installer from having to
program options for each device. Depending on the application, the installer may need to make some changes after JumpStart completes. See
Section 7.1.3 for complete details about running JumpStart.
7.1.1 Input Points
The first JumpStart on the panel in default configuration will determine the number and type of input points (detectors or contact monitor
modules) on each SLC loop. JumpStart Auto-Programming assigns the correct detector type (heat, ionization or photoelectric), so the
installer does not need to edit the device type for detectors. Any contact monitor modules on the system will be assigned type "Manual Pull."
The installer will need to manually change the switch type if manual pull is not correct.
The first JumpStart Auto-programming creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group
1. After JumpStart completes, you can re-map to configure a multiple zone/output group system. For a general explanation of mapping, see
Section 7.2.
7.1.2 Output Points
JumpStart Auto-programming creates three output groups and assigns output circuits as follows:
Configured as Notification and assigned to Group 1. JumpStart Auto-programming automatically programs Zone 1 to activate
Circuits 1-4:
Group 1 using constant on output when an alarm condition occurs.
Circuit 5 (Relay 1)
stant on output when a supervisory condition occurs.
Circuit 6 (Relay 2)
stant on output when an alarm occurs.
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases):
All addressable relay devices will be configured as "Output Pt" (general purpose output point) and assigned to Group 1.
NOTE: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
7.1.3 Running JumpStart Auto-programming
Run JumpStart Auto-Programming immediately after you have addressed and connected all input devices (detectors, pull stations, etc.) and
output devices (notification appliances, relays, etc.).
NOTE: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow instructions in Section 8 for
configuration.
To run JumpStart, follow these steps.
1.
Login to the panel and access the main menu.
2.
From the Main Menu Select 7 for the Program Menu.
3.
From the next menu, select 6 for JumpStart.
4.
When the message, "SLC FAMILY" message appears, select IDP, SK, or SD, depending on the type of SLC devices the panel is using,
and press ENTER to accept.
5.
A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several minutes,
depending on the number of devices attached.
6.
When the message "Configuring System Done" displays, press any key to continue.
IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022

Section 7: Programming Overview

Assigned to Group 249. JumpStart Auto-programming automatically programs Zone 1 to activate Group 249 using con-
Assigned to Group 250. JumpStart Auto-programming automatically programs Zone 1 to activate Group 250 using con-
77