IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Function
Latching Option
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Select Group
Select Group
01-80
Unused
NOTIF
Table 8.6 Programming Options for 5815XL Modules (Continued)
Performs identically to a supervisory switch, but will be indicated as a tamper
switch on the LCD annunciator.
Manual release switch
Interlock release switch input.
User also has ECS Event Number 1-8 option for ECS INPUT.
Only available when an ECS-VCM/ECS-NVCM is installed in the system.
CO Detector Switch
CO Supervisory Detector Switch
Output point, a general use notification type. Use for driving standard notification
appliances.
Use constant power for applications that require a constant auxiliary power
source. Power is always present at constant circuits. See "Constant Power" on
page 55 for more information.
Use for auxiliary power, resettable applications. See "Resettable Power" on
page 55 for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See "Door
Holder Power" on page 55 for a description of how this option operates.
Output point, a general use relay type. Use for applications requiring a relay, such
as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section "Resettable Power"
on page 55 for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See "Door
Holder Power" on page 55 for a description of how this option operates.
For use with SD devices only. 80 sub addresses on LED.
Notification can have group number.
Comments
Programming
105