RA-2000 Remote Annunciator
Installation Instruction
The RA-2000, an optional 4x40 Remote Annunciator,
is shown in Figure 1. The RA-2000 can be surface or
flush-mounted and is available in gray color as RA-
2000GRAY.
Figure 1: Model RA-2000GRAY Remote Annunciator
Compatibility
The RA-2000 is compatible with Honeywell's
Farenhyt Series FACP's.
Note: For more information, see the FACP Installation manual.
Specifications
Parameter
Operating Voltage:
24VDC
Standby: 25mA
Current
Alarm:
50mA
Operating
0° to 49° C (32° to 120° F)
Temperature:
Overall: 12¼" W x 11½" H x 7/8" D
Flush
(31.1 cm W x 29.2 cm H x 2.2 cm
Mount:
D) See "Flush Mounting" for back-
box dimensions.
Dimensions:
Including trim ring:
Surface
12¼" W x 11½" H x 3" D
Mount:
31.1 cm W x 29.2 cm H x 7.6 cm D
Mounting
Flush Mounting
Follow these steps to flush mount the RA-2000
1. The backbox measures 9-1/4" W x 8-3/8" H. The
2. Remove knockout holes as needed for wires.
Value
3. Wire the annunciator board to the main control
4. Attach the annunciator/door assembly to
backbox can be mounted prior to the complete
installation of the RA-2000 using any of the
mounting holes shown in Figure 2.
mounting holes
mounting holes
Figure 2: Backbox Mounting Holes
See Figure 3 for backbox knockout locations
wire knockouts
wire knockouts
Figure 3: Backbox Knockout Locations
panel. See Figure 7.
backbox as shown in Figure 4 using the supplied
wire knockouts
P/N 151443 Rev C
ECN 16-0218

Advertisement

loading

Summary of Contents for Honeywell Farenhyt Series

  • Page 1 Figure 1: Model RA-2000GRAY Remote Annunciator Compatibility mounting holes The RA-2000 is compatible with Honeywell’s Figure 2: Backbox Mounting Holes Farenhyt Series FACP's. 2. Remove knockout holes as needed for wires. See Figure 3 for backbox knockout locations Note: For more information, see the FACP Installation manual.
  • Page 2 Place the trim ring over the backbox as shown in Figure 6. Figure 6: Installing Trim Ring 5. Attach the annunicator/door assembly to the Farenhyt is a trademark, JumpStart and Honeywell are registered trademark of Honeywell International, Inc. ™ ® ® P/N 151443 Rev C ECN 16-0218...

This manual is also suitable for:

Ra-2000