Point; 1: Point Programming For 5815Xl Module - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

You can use words to display a descriptive name for a group.
NOTE: See Appendix B for editing names.
7.
Right arrow to the OPG and select YES or NO to select which output groups to include in the template.

9.5 Point

You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart. This section
explains how to change options for: type of point, latching/non-latching, silenceable/non-silenceable, zone assignment (input points),
detector accessory base options, group assignment (output points), and point name.
9.5.1 Point Programming For 5815XL Module
To program points on 5815XL Module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrows to select the desired module. Refer to Section 8.5 Quick Reference Table for available choices. Press
ENTER.
5.
Enter the number of the point you wish to edit, then press ENTER.
6.
Select the type of device by pressing the up or down arrow key. Refer to Table 9.3 under the column heading "Type Selection" for a
list of choices.
Type Selection
UNUSED
DETECTOR
SUP DET
SWITCH
120
Function
Latching Option
PHOTO
ION
HEAT
PHOTO DUCT
2-WIRE SMOKE
PHOTO
ION
Latching
Non Latching
HEAT
PHOTO DUCT
MANUAL PULL
Latching
WATERFLOW
Non Latching
Latching
FIRE SUPER-
VISORY
Non Latching
FIRE DRILL
SILENCE
RESET
Table 9.3 Programming Options for 5815XL Modules
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
2-wire smoke detector.
Use this option when you want a detector to indicate a supervisory
alarm.
Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This
switch type has the highest fire priority; it overrides any other type of
fire alarm.
Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can
be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a
water flow switch. The delay allows for normal, brief changes in
sprinkler system water pressure. The water flow alarm will not
activate unless the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a
water flow alarm is not generated. If the water flow switch remains
closed after the timer expires, a water flow alarm will be generated.
Use this switch type for tamper monitoring of sprinklers and other
fire protection devices. If a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches can be latching or
non-latching.
System-level, non latching switch. This switch is an alternative way
of causing a fire drill. It has the same operation as the fire drill option
available from the annunciator. When the switch is activated, a fire
drill begins; when the switch is de-activated, the fire drill ends.
This system-level switch is an alternative way to silence the fire
system. It has the same effect as pressing the Silence key.
This system-level switch is an alternative way to reset the fire
system. It has the same effect as pressing the Reset key.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017