RA-1000 Remote Annunciator Installation

4.6 RA-1000 Remote Annunciator Installation
The optional Model RA-1000 Remote Annunciator, is shown in Figure 4.20. Up to 8 annunciators can be added to the IFP-75 System.
RA-1000 installation involves the following steps.
1.
Make sure the power is off at the panel.
2.
Mount the RA-1000 in the desired location (see Section 4.6.1).
3.
Connect the RA-1000 to the panel (see Section 4).
4.
Use the dip switches on the back of the RA-1000 to assign an ID# to the RA-1000 (see Section 4.11.1).
5.
The new RA-1000 module must be added to the System through programming. JumpStart will add the module automatically (see
Section 8.1). You can also add the module manually (see Section 8.2.2). Select a name, if desired.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Figure 4.20 Model RA-1000 Remote Annunciator, Front View