Honeywell IFP-75 Installation & Operation Manual page 95

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Point
Type
Function
Selection
SWITCH
MAN_PULL
(cont.)
WATERFLOW
SUPERVSY
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
DETECT SW
SWITCH
TAMPER
(cont.)
MAN REL
ILOCK
CO DETECT SW
CO SUPERVISORY
DETECT SW
STATUS PT
NOTIF
OUTPUT PT
AUX CONST
AUX RESET
AUX DOOR
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Latching Option
Use this switch type for manual pull stations. This input is always latched. The switch can
clear only when an alarm is reset.
Latching
Use this switch type for monitoring water flow in a Sprinkler System. Switch closure will
Non Latching
cause a sprinkler alarm. Water flow switches can be programmed as latching or non-
latching.
You can program a delay of up to 90 seconds to be used with a water flow switch. The
delay allows for normal, brief changes in Sprinkler System water pressure. The water flow
alarm will not activate unless the switch is active for the programmed delay time.
Note:
onds.
If a delay is used, the System begins counting down when the switch closes. If the switch
opens (restores) before the timer expires, a water flow alarm is not generated. If the water
flow switch remains closed after the timer expires, a water flow alarm will be generated.
Latching
Use this switch type for tamper monitoring of sprinklers and other fire protection devices. If
Non Latching
a contact closes, a sprinkler supervisory event will be generated. Supervisory switches
can be latching or non-latching.
System-level, non latching switch. This switch is an alternative way of causing a fire drill. It
has the same operation as the fire drill option available from the annunciator. When the
switch is activated, a fire drill begins; when the switch is de-activated, a fire drill ends.
System-level switch provides an alternate way to silence the System; same effect as
pressing the Silence key.
System-level switch provides an alternate way to reset the System; same effect as
pressing the Reset key.
Positive acknowledge switch. This switch must be used in zones programmed as Positive
Alarm Sequence (see Table 9.2).
If an acknowledge switch closes when an alarm or trouble condition is not already in
progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The switch must be rated
at 5V, 100 mA (minimum) and be used with an EOL resistor for supervision.
Latching
Use these switch types if you want to monitor special zone-level conditions.
Non Latching
Latching
Non Latching
Latching
Use these switch types if you want to monitor special system-wide conditions.
Non Latching
Latching
Non Latching
Used to monitor conventional 4-wire detectors, a contact closure will generate a detector
alarm event.
Latching
Performs identically to a supervisory switch, but will be indicated as a tamper switch on the
LCD annunciator.
Non Latching
Manual release switch, typically a pull station.
Interlock release switch input.
CO Detector Switch
CO Supervisory Detector Switch
Status Point Switch
Select Group
Output Point, a general use notification type. Use for driving standard notification
appliances.
Use constant power for applications that require a constant auxiliary power source. Power
is always present at Constant circuits.
Use for auxiliary power, resettable applications. See Section 4.13.2 (subsection,
Resettable Power) to learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See Section 4.13.2
(subsection, Door Holder Power) to learn how this option operates.
Table 9.4 Point Programming for Internal SLC Module (Continued)
Comments
Waterflow delay of the FACP and the waterflow device shall not exceed 90 sec-
Programming
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents