About This Manual; 1: Terms Used In This Manual; Compatible Products - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Introduction

1.2 About this Manual

1.2.1 Terms Used in this Manual
The following terminology is used with the IFP-75 System:
Term
SLC
Module
Input Point
Input Zone
Output Point (or Output Circuit)
Group (or "Output Group")
Output (or "Cadence") Pattern
Mapping
Network System
SWIFT

1.3 Compatible Products

The chart below lists the products available for use with the IFP-75.
Type of Device
IDP Addressable SLC Devices
SWIFT Wireless SLC Devices For information on the compatible SWIFT Devices, refer to the SWIFT manual #LS10036-000FH-E.
Other Modules Wireless
Wireless
10
Signaling Line Circuit
The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the IFP-75 panel itself.
An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
A protected area made up of input points.
A notification point or circuit used for notification appliances. Relay circuits and auxiliary power circuits are
also considered output points.
A group of output points. Operating characteristics are common to all output points in the group.
The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones and
special system events. See Appendix D for additional information.
Mapping is the process of specifying which outputs are activated when certain events occur in the System.
Section 8, Figure 8.2 explains mapping in detail.
Consist of any combination of 32 panels of these model numbers: IFP-75, IFP-300, IFP-300ECS, IFP-2100
or IFP-2100,ECS, IFP-75.
Smart Wireless Integrated Fire Technology
Table 1.1 Manual Terminology
Model
For information on the compatible Addressable SLC Devices, refer Chapter 7.
5824 Serial/Parallel Printer
Allows a printer to be attached for the on-site event logging. Maximum of four
Interface Module
5824 modules per control panel.
RPS-1000 Power Supply
Provides additional power, six Flexput circuits, and two Form C relays. Max 8 per
System. See RPS-1000 Installation Manual (PN 151153) for more information.
5496 NAC Expander
Provides 4 additional Notification Appliance Circuits/Auxiliary power.
(Up to 8 per IFP-75 System.)
RA-100 and RA-100R LCD
4 x20 Remote LCD annunciator. can be used in any combination, up to a total of 8
Annunciator
devices on one panel.
RA-1000 and RA-1000R
4 x20 Remote LCD annunciator can be used in any combination, up to a total of 8
LCD Annunciator
devices on one panel.
RA-2000 LCD Annunciator 4 x 40 Remote LCD annunciator can be used in any combination, up to a total
of 8 devices on one panel.
5865-3 and 5865-4 LED
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has
Annunciator
key switches for silence and reset, and a system trouble LED. 5865-3, 5865-4, and
5880 can be used in any combination, up to a total of eight devices on one panel.
RA-100TG and RA-100TR
Trim ring kits for surface mounting the RA-100/RA-100R annunciator. RA-100TG is
Trim Ring
gray; RA-100TR is red.
5860TG and
Trim ring kits for surface mounting theRA-1000 annunciator. 5860TG is gray;
5860TR Trim Rings
5860TR is red.
5880 LED Driver Module
Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In
addition the 5880 has eight generic switch input points.
5883 General Purpose
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four,
Relay Module
5883 relays can be used with each 5880 module.
SK-NIC
Network Interface Card
SK-FML
Fiber-Optic Multi Mode
SK-FSL
Fiber-Optic Single Mode
IDP-WGI
Wireless Gateway
IDP-PHOTO
Wireless Photoelectric Smoke Detector with 4" base
WIDP-ACCLIMATE
Wireless Multi criteria photoelectric smoke detector with thermal (135°F) with 4"
base
WIDP-HEAT-ROR
Wireless ROR Heat Detector heat, ROR/ 135° fixed with 4" base
WIDP-HEAT
Wireless Heat, 135° Fixed Heat Detector with 4" base
WIDP-MONITOR
Wireless Addressable Monitor module
Table 1.2 IFP-75 Compatible Products
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Description
Description
About this Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents