Honeywell IFP-75 Installation & Operation Manual page 97

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Point
Choices
Type Selections
Enter Point or Circuit
Select Type
UNUSED
NOTIF OUT
CTRL CKT
AUX PWR
B SWITCH*
A SWITCH*
B DETECTOR*
A DETECTOR*
Select Group
Edit Name
*Only applicable on RPS-1000
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Function Selections
for each Type
CONSTANT
RESETTABLE
DOOR
AUX SYNC
MAN PULL
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
STATUS POINT
Same as B SWITCH
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
Table 9.5 Menu Choices for Internal/External Power Modules
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Sounder Sync auxiliary power for System Sensor
Refer to comments column of
Table 9.4 for description of these options
Latch or Non-latching feature only appears for waterflow, supervisory, tamper,
zone aux1, zone aux2, system aux1, and system aux2
Non-latching - Used to activate an ancillary Output Group that does not active
alarm, sound PZT, display status or report events. Reset has no affect on this
point
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire CO Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-wire CO Supervisory detectors
Group or Zone selection will appear depending on the type selected
Edit name. See Section 9.5.3
Comments
Programming
97