Telephone Connection

4.12 Telephone Connection
Connect the telephone lines as shown in Figure 4.44. The Model 7860 phone cord is available from Honeywell for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6.

4.13 Notification Appliance/Auxiliary Power Circuits

Two outputs are built-in to the IFP-75FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power. This sec-
tion of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
4.13.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A and Class B configurations.
Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 4.45.
2.
Configure the circuit through programming (see Section 8.5).
.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Figure 4.44 Connection of Telephone Lines
Figure 4.45 Class B Notification Appliance Circuit Wiring
Control Panel Installation
Notification Wiring
supervised
power limited
47