Wiring Specifications - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Wiring Specifications

3.5 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To
avoid induced noise, follow these guidelines:
Isolate input wiring from the high current output and the power wiring. Do not pull one multi-conductor cable for the entire panel.
Instead, separate the wiring as follows:
Do not pull wires from the different groups through the same conduit. If you must run the wires together, do so for as short a distance as
possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board, where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3.1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire
through ferrite shield beads or by wrapping it around a ferrite toroid.
Note: 1/4" spacing
must t be maintained
between each of
these circuit types;
as well as between
power limited and
non-power-limited
circuits.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
High Voltage
SLC loops
Audio input/output
Notification circuits
SBUS
Relay circuits
Table 3.2 Wiring Specifications
AC Power
Input
Relay
Outputs
Phone
Lines
Battery
Figure 3.1 Wire Routing Example
AC power Terminals
Phone line circuits
NAC1 through NAC2
Battery
Prerequisites for Installation
NAC / Aux Power
Outputs
SBUS
Devices
SLC IN/OUT
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents