Section 2: Agency Listings, Approvals, and Requirements

Install and maintain this panel in accordance with NFPA 72. Detector spacing shall be done in accordance to NFPA 72. End-of -line relays
and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be per-
formed in compliance with NFPA 72.

2.1 Federal Communications Commission (FCC)

The following information must be provided to the Telephone Company before the IFP-75 can be connected to the phone lines:
1.
This device may not be directly connected to coin telephone or party line services.
2.
This device cannot be adjusted or repaired in the field. In case of an issue with the device, notify the installing company or return it to:
3.
Honeywell Farenhyt
12 Clintonville Road
Northford, CT 06472-1610
(203) 484-7161
If the IFP-75 causes harm to the telephone network, the Telephone Company will notify the user in advance that temporary
discontinuance of service may be required. If advance notice is not practical, the Telephone Company will notify the user as soon as
possible. Users have the right to file complaints, if necessary, with the Federal Communications Commission.
4.
The Telephone Company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the
equipment. If this happens, the Telephone Company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
WARNING: FCC RULES PART 15
!
THIS DEVICE HAS BEEN VERIFIED TO COMPLY WITH FCC RULES PART 15. OPERATION IS SUBJECT TO THE
FOLLOWING CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE RADIO INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
1.
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the wiring diagram of this
equipment is a label that contains, among other information, a product identifier in the format US: HS9AL10A2100. If requested,
this number must be provided to the Telephone Company.
2.
See manual for phone jack information.
3.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable
FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug is provided with this
product. It is designed to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
4.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be
connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the
number of devices is limited. The REN number is embedded in the FCC registration number as 10A.
5.
If this equipment IFP-75 causes harm to the telephone network, the Telephone Company will notify you in advance that temporary
discontinuance of service may be required. But if advance notice isn't practical, the Telephone Company will notify the customer
as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
6.
The Telephone Company may make changes in its facilities, equipment, operations or procedures that could affect the operation of
the equipment. If this happens the Telephone Company will provide advance notice in order for you to make necessary
modifications to maintain uninterrupted service.
7.
If trouble is experienced with the IFP-75, for repair or warranty information, please contact Honeywell technical support at 800-
446-6444 or www.
request that you disconnect the IFP-75 until the problem is resolved.
8.
See warranty in back of this manual for repair and replacement information.
9.
Connection to party line service is subject to state tariffs. Contact the state public utility commission, public service commission or
corporation commission for information.
10. If your building has specially wired alarm equipment connected to the telephone line, ensure the installation of this IFP-75 does
not disable your alarm equipment. If you have questions about what device will disable alarm equipment, consult your Telephone
Company or qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory notice in their customer information suggesting
the customer use a surge arrestor. Telephone companies report that electrical surges, typically lightning transients, are very destructive to
customer terminal equipment connected to AC power sources. This has been identified as a major nationwide problem.
12
A
Manufacturer:
B
Model Number:
C
FCC registration number:
Ringer equivalence:
D
Type of jack:
E
Facility Interface Codes:
F
Service Order Code:
farenhyt.com
. If the equipment is causing harm to the telephone network, the Telephone Company may
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021