Addressing Idpslc Devices; Sd Detector Installation - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Addressing IDPSLC Devices

7.7 Addressing IDPSLC Devices
All IDP devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a
one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
The IDP device addresses are handled differently than SDdevice addresses. The control panel recognizes when a IDP detector or the IDP
module is installed. For this reason, the IDP detectors can be assigned any unique address from 1 to 75, and the IDP modules can be assigned
any unique address from 1 to 75. There can be a IDP detector using address 1 and a IDP module using address 1. The zero, 0, is an invalid
address.
NOTE: Any device addressed over 50 will not be recognized by the panel.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in Figure 7.4 .
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 7.4.
ik
Example 1: Device Set to 01.

7.8 SD Detector Installation

The information in this section applies to the following SD models, see Table 7.3 for the list of devices.
1.
Wire the device bases as shown in Figure 7.5.
2.
Set the address for each device as described in Section Figure 7.9.
.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Example 2: Device Set to 42.
Figure 7.4 IDPSLC Device Addressing Using Rotary Dials
Figure 7.5 Heat or Smoke Detector Connection to the FACP (Class B)
IDP, SK, SD and SWIFT SLC Device Installation
All dials labeled for ONES
or TENS position.
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents