Section 1: Introduction; Overview Of Basic System; 1: Hardware Features; 2: Network System Hardware Features - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

The IFP-75 (red) / IFP-75B (black) are IFP-75 Fire Alarm Control / Communicators that operate as an Addressable Fire Alarm Control Panel
System that complies with the requirements of UL 864 10th Edition Standard.
NOTE: *All references to IFP-75 within this manual are applicable to the IFP-75, IFP-75B, IFP-75HV and IFP-75HVB unless otherwise
specified.

1.1 Overview of Basic System

1.1.1 Hardware Features
The IFP-75 has one built-in signaling line circuit (SLC) that supports 75 IDP detectors and75 IDP modules or 50 SD protocol devices.
The IFP-75 is capable of outputting 2.5A of output power during the alarm activation through 2 sets of terminals for notification
appliance circuits or auxiliary application. Each circuit is power-limited and can source up to 2.5A during an alarm activation. The
constant auxiliary power load must not exceed 1A for the normal standby.
NOTE: Total output power used for both circuits must not exceed 2.5A in alarm condition, and total output power used for both circuits must not
exceed 1.0A for all other activation conditions (i.e. Supervisory, Trouble, etc.).
Built-in dual phone line, Digital Alarm Communicator/Transmitter (DACT), IP, or optional cellular technologies. Reports events to the
Central Station by point or by zone.
UL Listed for pre-action and Deluge Releasing Systems.
Two general purpose Form C programmable relays.
One Form C Trouble Relay.
Basic system operation can be performed from the on-board or any remote annunciator.
Up to 20 user profiles can be programmed, each having a custom Access Code, and Main Menu items.
Can be used with any combination of up to 8 Model RA-100, RA-1000, or RA-2000 Remote LCD Annunciators (sold separately).
Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one control panel. See Figure 4.31
and Figure 4.34 for additional information on these models.
Printing of event log available through the Model 5824 serial/parallel printer interface module.
125 software zones, 125 Output Groups.
Add four Notification/Auxiliary power circuits with each FIK-5496 NAC Expander. See note below.
NOTE: The system can support a maximum of eight intelligent power modules, either the RPS-1000 or 5496, in any combination.
1.1.2 Network System Hardware Features
The default network setup can contain up to 32- IDP-75 panels connected.
Network support for up to 32 Sites.
Each building is referred to as a "site".
Panels can be interconnected using CLASS B or CLASS A topology.
Use the SK-NIC Network Interface Card to create a network. Copper wire or fiber-optic cable panel connectivity can be used within the
same networked system.
The network architecture provides true peer-to-peer capability allowing network survivability for all hardware that remains operational
in the event of a partial system failure.
1.1.3 Software Features
The following list the features.
The network architecture provides true peer-to-peer capability allowing network survivability for all hardware that remains operational
in the event of a partial system failure.
Advanced smoke detector features:
– Automatic drift compensation
– Maintenance alert region
– Point status meets calibrated smoke test requirements for NFPA 72
JumpStart feature for easy programming
Non-volatile event history stores 1,000 events
A choice of output patterns available for notification outputs, including Temp 4 along with ANSI 3.41 temporal signal
Built-in synchronization appliance support for AMSECO, Gentex, Wheelock, or System Sensor
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021

Section 1: Introduction

9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents