Honeywell IFP-75 Installation & Operation Manual page 118

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Reporting
Event Description
Fire System Overridden
Fire System Override Restore
Ground fault condition trouble
Ground fault condition trouble restore
Initial power up
Local programming aborted or ended
with errors
Local programming begin
Local programming ended normally
Network node trouble (panel missing)
Network node trouble restore
(panel no longer missing)
OPG Inhibit Trouble
OPG Inhibit Trouble Restore
OPG Inhibit of Releasing Group
OPG Inhibit of Releasing Group Restore
Phone line 1 trouble detected
Phone line 1 trouble restore
Phone line 2 trouble detected
Phone line 2 trouble restore
Printer is off-line trouble
Printer is off-line trouble restore
Printer is out of paper trouble
Printer is out of paper trouble restore
Releasing Notif/Control Circuit Disabled pi Exp. ID SS
Releasing Notif/Control Circuit enabled pi Exp. ID SR
Remote programming aborted or ended
with errors
Remote programming ended normally
Repeater ground fault trouble
Repeater ground fault trouble restore
Repeater missing trouble
Repeater missing trouble restore
Repeater Rx1 communication trouble
Repeater Rx1 communication trouble re-
store
Repeater Rx2 communication trouble
Repeater Rx2 communication trouble re-
store
SBUS Class A supervision lost
SBUS Class A supervision restore
SBUS expander trouble
SBUS expander trouble restore
SLC class A supervision trouble
SLC class A supervision trouble restore
118
SIA Reporting Format
SIA pi Modifier
Module ID
SIA
Parameter
# (If Any)
Event
Codes
FS
0
FR
0
YP
Exp. ID
YQ
Exp. ID
RR
0
LU
0
LB
0
LS
0
EM
Panel ID
EN
Panel ID
FT
Group # + 1000
FJ
Group # + 1000
SS
Group # + 1000
SR
Group # + 1000
LT
1
LR
1
LT
2
LR
2
VZ
Exp. ID
VY
Exp. ID
VO
Exp. ID
VI
Exp. ID
Point #
Point #
RU
0
RS
0
EM
0103
EN
0103
EM
0100
EN
0100
EM
0101
EN
0101
EM
0102
EN
0102
ET
Exp. ID
ER
Exp. ID
ET
Exp. ID
ER
Exp. ID
ET
Exp. ID
ER
Exp. ID
Table 11.2 Reporting Formats Table (Continued)
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Receivers Compatible with the Control Panel
Contact ID Reporting Format
SIA
Fixed Length
Qualifier
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
FSNN000000
1
FRNN000000
3
YPNNXX0000
1
YQNNXX0000
3
RRNN000000
1
LUNN000000
1
LBNN000000
1
LSNN000000
1
EMNNNN0000
1
ENNNNN0000
3
FTNN001GGG
1
FJNN001GGG
3
SSNN001GGG
1
SRNN001GGG
3
LTNN000001
1
LRNN000001
3
LTNN000002
1
LRNN000002
3
VZNNXX0000
1
VYNNXX0000
3
VONNXX0000
1
VINNXX0000
3
SSNNXXPPPP
1
SRNNXXPPPP
3
RUNN000000
1
RSNN000000
1
EMNN000103
1
ENNN000103
3
EMNN000100
1
ENNN000100
3
EMNN000101
1
ENNN000101
3
EMNN000102
1
ENNN000102
3
ETNNXX0000
1
ERNNXX0000
3
ETNNXX0000
1
ERNNXX0000
3
ETNNXX0000
1
ERNNXX0000
3
Event
Group #
Contact #
Code
245
00
000
245
00
000
310
Exp. ID
000
310
Exp. ID
000
305
00
000
628
00
000
627
00
000
628
00
000
334
Panel ID
000
334
Panel ID
000
320
00
Group #
320
00
Group #
203
00
Group #
203
00
Group #
351
00
000
351
00
000
352
00
000
352
00
000
336
Exp. ID
000
336
Exp. ID
000
335
Exp. ID
000
335
Exp. ID
000
203
Exp. ID
Point #
203
Exp. ID
Point #
413
00
000
412
00
000
334
Panel ID
103
334
Panel ID
103
334
Panel ID
100
334
Panel ID
100
334
Panel ID
101
334
Panel ID
101
334
Panel ID
102
334
Panel ID
102
333
Exp. ID
000
333
Exp. ID
000
333
Exp. ID
000
333
Exp. ID
000
331
Exp. ID
000
331
Exp. ID
000

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents