5880 LED Driver Module
4.9.2 FACP Connection
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4.36. After the 5880 is connected to the panel, it must
be added to the System. This programming step is described in Section 8.
4.9.3 LED Wiring
There are four 12-pin connectors on the 5880 board that are used to connect the LEDs. Each LED gets its power from Pin 11. The Internal
Resistors are sized so that there is approximately 10 mA of current for each LED; no series resistors are required. The LED outputs can be
mapped to output circuits. See Section 8 for Programming details.
Wire the LEDs as shown in Figure 4.37.
On connector P1, Pin 12 is a programmable Open Collector Output that is used to control a PZT. If used, the 5880 PZT will match the PZT
pattern of the on-board or remote annunciator.
NOTE: The circuit connected to "Open Collector Output" (last pin on P1) must be current-limited so that no more than 100 mA of current is
allowed to flow into the Open Collector Transistor.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
supervised
power-limited
Figure 4.36 5880 Connection to Main Control Panel Assembly
Figure 4.37 5880 Board Layout
Control Panel Installation
43