Programming
9.6.4 Time Options
Usethis programming option to set the following:
water flow delay time
enable or disable automatic daylight savings time adjustment
Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow switch. The delay is system-
wide. All water flow switches on the System will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
Select 4 to access the Time Options.
A screen similar to the one shown in Figure 9.13 will display.
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow or press ENTER to make your selection and move the cursor to the next programming option.
AC Report Delay
NOTE: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:.
8.
Enter the number of hours before a low AC report will be sent to the central station, then press ENTER.
AC Line Frequency
The panel's AC line frequency is selectable for 50 or 60 Hz or Internal. AC Frequency feature dictates how the control panel will calculate
time based on the AC line frequency used in the installation site. The "Internal" option can be used in areas where the AC line frequency is
not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power
source and internal 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz. selection.
To change the AC line frequency, continue programming from steps above:
9.
Select 50 Hz, 60 Hz or Intl, by pressing the up or down arrow key. Then, press ENTER.
Clock Display Format (AM/PM or Military)
To change the System Clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then press
ENTER.
Auto-Resound (4 or 24 hours)
The System resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto-
matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices.
102
low AC report delay
Figure 9.13 Water Flow Delay Programming Screen
Figure 9.14 Low AC Report Delay Programming Screen
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
clock format,
AC clock frequency.
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
Low AC Report delay
in hours (00-30)
System Options