3: I/O Point Control; Earth Fault Resistance - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Earth Fault Resistance

12.3.3 I/O Point Control
NOTE: Once you exit the system will resume normal operation.
This feature allows you to toggle any Output on or off and trip any Input device. This option can be useful to test a Point's Output Mapping.
Follow these steps to control a I/O Point:
1.
From the Main Menu, select 2 (Point Functions).
2.
Select 6 (I/O Point Control).
3.
Select the Module the point is on.
4.
Enter the Point Number, or press the up or down arrow to select the point you want to test, then press ENTER.
5.
Press ENTER to generate an alarm for an Input Point or activate an Output Point.
6.
To exit, press the left arrow key.
12.4 Earth Fault Resistance
Table 12.2 lists the Earth Fault Resistance Detection for each applicable terminal on the FACP.
NAC 1 -
NAC 1 +
NAC 2 -
NAC 2 +
SBUS -
SBUS +
SBUS A
SBUS B
SLC IN -
SLC IN +
SLC OUT -
SLC OUT +
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
TERMINAL
(values in kohms)
high trip
0
0
0
0
0
LOW BIASED
high restore
0
0
0
0
0
Table 12.2 Earth Fault Resistance