Programming
9.6.8 SLC Family
The IFP-75supports SD, SK Series, or Intelligent Device Protocol (IDP)SLC devices. You must configure the IFP-75 to accept the protocol
of the devices you are installingYou cannot mix SLC devices of different protocols.
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
Select 8 for SLC Family.
5.
Press UP arrow to select the desired SLC device type.
6.
Press ENTER to accept the displayed SLC device type.
When you change the SLC type from one protocol to another, the following message will appear.
9.7 JumpStart Auto-Programming
Panels support an incremental JumpStart. For Example: After the initial JumpStart and customization, if you add more devices, when you
JumpStart again, the additional devices are added. However, you do not lose any of your previous custom programming.
To run JumpStart Auto-Programming:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 6 to access the JumpStart Auto-Programming.
4.
From the Warning screen, press the up or down arrow to select "Yes".
5.
Press ENTER.
9.8 Restore Defaults
This option allows you to restore the panel back to factory defaults. All programming will be lost.
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 to access the Panel Programming.
3.
Select 7 for Restore Defaults.
4.
From the Warning screen, press the up or down arrow keys to select YES or NO. Then, press ENTER.
104
Figure 9.15 SLC Family Change
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
JumpStart Auto-Programming