F.1 ANN-LED Annunciator Installation for Canadian Applications
The FACP is supplied with a modified dress panel and one ANN-LED annunciator.
When installing and programming the FACP, the Canadian Option must be set to ON prior to any other panel programming (refer to
"Canadian Option" on page 70 of the Programming Section of this manual).
If remote indicators are desired, they must be connected to the secondary ANN-BUS circuit. This requires the use of the ANN-SEC
option card.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty Label located on the FACP backbox
door.
To comply with CAN/ULC-S559-04, the ANN-RLY option must be utilized along with the configuration shown in Figure F.2.
ANN-LED Annunciator
on Primary ANN-BUS
128

Appendix F: Canadian Applications

FACP
Figure F.1 Canadian FACP Configuration
Optional Secondary
ANN-BUS using
ANN-SEC Option Card.
ANN-S/PG
ANN-RLY
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
ANN-LED
ANN-80C
ANN-I/O