2: Adding A Module; 3: Deleting A Module; 4: View Module List; Zone - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

Zone

Changing Module Options
Each module has a unique set of options that specifically applies to the functionality of the module being edited.
8.
Use the left and right arrow keys to move between available options.
9.
To edit Option settings, press the up or down arrow.
9.2.2 Adding a Module
You must acccess the Main Menu to perform this task. If necessary, enter the Installer Code. If you need to add a new hardware module to the
System, follow the steps below.
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 1 to enter the Module Menu.
4.
Press 2 to add a module.
5.
From the next screen, use the up or down arrow to choose a module type to add from the <New Module Type> screen.
The screen will display "Adding module [#]..." for a few moments. You will be returned to the <New Module Type> screen where you
can select another module if desired.
Save the changes when you exit the Program Menu or the System will not add the new module.
NOTE: If you add a module that has not been physically connected, the panel will go into trouble after it reinitializes (when you exit the
Program Menu). When the new module is attached, the trouble will automatically correct itself.
9.2.3 Deleting a Module
To delete a module, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 1 to enter the Module Menu.
4.
Press 3 to delete a module.
5.
From the next screen, select a module to delete. A warning screen will display.
6.
If you want to proceed and delete the module, select Yes. To cancel, select No.
9.2.4 View Module List
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 1 to enter the Module Menu.
4.
Press 4 to view the Module List.
9.3 Zone
Use the Zone Option in the Program Menu to edit, add, delete, and view Zone Points. The selections you make affect all detectors and
switches in the zone. Up to 125 zones can be used in the System.
9.3.1 Edit Zone
At the Edit Zone Option, the features you can edit are the following:
zone name
zone properties (which includes, zone type and detector sensitivity)
zone accessory options
To edit a zone, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 2 to enter the Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the Zone Number, then press ENTER.
Edit Zone Name
6.
To edit the Zone Name, press 1.
You can enter a description to display a descriptive name for the zone.
NOTE: See Appendix B for information to edit names.
Edit Zone Properties
Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1.
Do steps 1 through 5 of Section 9.3.1.
2.
Press 2 to edit the properties of the selected zone.
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
Programming
89