Testing and Troubleshooting
12.2.2 Event History
The event history can be useful for tracking or recalling a trouble condition.

12.3 Built-in Troubleshooting and Testing Tools

The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and troubleshooting
points and SLC devices.
12.3.1 SLC Device Locator
SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1.
Select 2 (Point Functions) from the Main Menu.
2.
Select 4 (SLC Dev Locator).
A message similar to the one shown in Figure 12.1 will display.
3.
Press the up or down arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function Menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6.
Press left arrow to exit SLC device locator function.
NOTE: Once you exit the system will resume normal operation.
12.3.2 SLC Multi Locator
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a single search.
Follow these instructions to locate multiple SLC devices:
1.
Select 2 (Point Functions) from the Main Menu.
2.
Select 5 (SLC Multi Locator).
A message similar to the one shown in Figure 12.1 will display.
3.
Press the up or down arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function Menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6.
Press the left arrow key to exit SLC multi-locater function.