This Section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you install the IFP-75 panel for the first time.

3.1 Inventory

When the IFP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of
the following:
main circuit board with the display
backbox with door
plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
manual

3.2 Environmental Specifications

It is important to protect the IFP-75 control panel from water. To prevent water damage, the following precautions should be followed when
you install the units:
Intended for indoor use in dry locations only.
Do not mount the panel directly on exterior walls, especially masonry walls (condensation).
Do not mount the panel directly on exterior walls below grade (condensation).
Protect the panel from plumbing leaks.
Protect the panel from splash caused by Sprinkler System inspection ports.
Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the IFP-75 control panel, the unit should be mounted where it will NOT be exposed to temperatures out-
side the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.

3.3 Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you install and program the latest features, we strongly recommend that you down-
load the most current version of software for each product prior to commissioning any System. Contact Technical Support with any ques-
tions about software and the appropriate version for a specific application. The HFSS Honeywell Fire Software Suite is available at
www.farenhyt.com.

3.4 Electrical Specifications

Table 3.1 lists the terminal block on the IFP-75 as well as a description of each individual terminal and their respective electrical rating. For
information on the location of the terminals, refer to Figure 3.2. See also Section 4 for the installation information.
Terminal No.
Terminal Block 3
TELCO 1
PHONE 1
TELCO 2
PHONE 2
Terminal Block 2
RELAY 1
RELAY 2
TROUBLE
SLC IN
SLC OUT
SLC PROG
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021

Section 3: Prerequisites for Installation

Label
Group
Individual
RING
TIP
RING
TIP
RING
TIP
RING
TIP
NO
COM
NC
NO
COM
NC
NO
COM
NC
+
+
+
Table 3.1 Terminal Descriptions and Electrical Specifications
Description
Phone Line 1 Telco Ring
Phone Line 1 Telco Tip
Phone Line 1 Phone Ring
Phone Line 1 Phone Tip
Phone Line 2 Telco Ring
Phone Line 2 Telco Tip
Phone Line 2 Phone Ring
Phone Line 2 Phone Tip
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Used for Class A installations
SLC terminals
Used for programming SLC Detectors
Rating
Voltage
Current
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
32 VDC
100 mA
32 VDC
100 mA
32 VDC
100 mA