Section 8: Programming Overview; Jumpstart Auto-Programming; 1: Input Points; 2: Output Points - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Hide thumbs Also See for IFP-75:
Table of Contents

Advertisement

This Section of the manual is intended to give you an overview of the Programming process. Please read this section of the manual carefully,
especially if you are programming the control panel for the first time.
The JumpStart Auto-Programming feature automates many programming tasks and selects the default options for the System. You will run
the JumpStart Auto-Programming at least once when you install the System. See Section 8.1 for details. After you run the JumpStart Auto-
Programming, you may need to do some additional programming, depending on your installation. Section 8 of this manual covers manual
programmable options in detail.
Programming the panel can be thought of as a three part process. You must program the following:
System options. These are options that affect the general operation of the panel (see Section 9.6 for details).
Options for input points and zones. These are primarily options that control the detection behavior of the devices (see Section 8.3 and
Section 8.5 for details).
Options for output points and groups. These options include selecting characteristics for Output Groups and mapping output circuits to
Output Groups (see Section 8.4 and Section 8.5 for details).

8.1 JumpStart Auto-Programming

The JumpStart Auto-Programming feature allows for a faster system setup. When you run the JumpStart Auto-Programming (immediately
after addressing SLC devices), the System scans devices on all SLC loops and determines the device type (for example, photoelectric smoke
detector or heat sensor) and selects some system options based on the device type. This feature saves the Installer from having to program
options for each device. Depending on the application, the Installer may need to make some changes after the JumpStart Auto-Programming
completes.
See Section 8.1.3 for complete details about running JumpStart Auto-Programming.
WARNING: JUMPSTART AUTO-PROGRAMMING PRECAUTION
!
JUMPSTART AUTO-PROGRAMMING IS INTENDED TO BE RUN ONE TIME ONLY, IMMEDIATELY AFTER SLC DEVICES
HAVE BEEN ADDRESSED AND CONNECTED. JUMPSTART AUTO-PROGRAMMING WILL RESET ALL MANUALLY
PROGRAMMED OPTIONS TO DEFAULT SETTINGS. DO NOT RUN JUMPSTART AFTER YOU HAVE CONFIGURED THE
SYSTEM
.
8.1.1 Input Points
JumpStart Auto-Programming will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop.
JumpStart Auto-Programming assigns the correct detector type (heat, or photoelectric), so the installer does not need to edit device type for
detectors. Any contact monitor modules on the System will be assigned type "Manual Pull." The installer will need to manually change the
switch type if manual pull is not correct.
JumpStart Auto-Programming creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1.
8.1.2 Output Points
The JumpStart Auto-Programming creates three Output Groups and assigns output circuits as follows:
Circuits 1-2:
Configured as Notification and assigned to Group 1. JumpStart Auto-Programming automatically programs Zone 1 to activate Group 1
using constant on output when an alarm condition occurs.
Circuit 3 (Relay 1):
Assigned to Group 124. JumpStart Auto-Programming automatically programs Zone 1 to activate Group 124 using constant on output
when a supervisory condition occurs.
Circuit 4 (Relay 2):
Assigned to Group 125. JumpStart Auto-Programming automatically programs Zone 1 to activate Group 125 using constant on output
when an alarm occurs.
Addressable output points (Relay modules):
All addressable relay devices will be configured as "Output Pt" (general purpose output point) and assigned to Group 1.
NOTE: The Relay output is constant even if the zone activating the relay is programmed with an output pattern.
8.1.3 Running JumpStart Auto-Programming
Run the JumpStart Auto-Programming immediately after you address and connect all the input devices (detectors, pull stations, and so on)
and output devices (notification appliances, relays, and so on).
NOTE: To install a few devices manually after running JumpStart, see Section 8.
To run the JumpStart Auto-Programming, do the following steps.
1.
Press ENTER to view the Main Menu.
2.
Select 7 for the Program Menu.
3.
From the next Menu, select 6 for JumpStart.
4.
When the message, "SLC FAMILY" message appears, select theIDP, SK Series, or SD; depending on the type of SLC devices the panel
is using, and press ENTER to accept.
5.
A series of messages display for the next several seconds. JumpStart scans the SLC loops for the devices. This process can take several
minutes, depending on the number of devices attached.
74

Section 8: Programming Overview

IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt seriesIfp-75hv

Table of Contents