System Operation
5.
To End the Walk Test, access the Main Menu. Select 1 for the System Test, then press 3 or 4.
6.
Press ENTER to end the Walk Test. The System will reset. The panel will send a "TEST RESTORE" report to the Central
Station.
If you do not manually end the Walk Test within four hours, it will end automatically. If an alarm or pre-alarm condition is
occurring in the System, you will not be able to enter the Walk Test.
NOTE: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is returned to normal,
the panel is ready to access the next device.
10.4.7 Conduct a Communicator Test
1.
From the Main Menu, press 1 to access the System Tests.
2.
Select 5 to access the Communicator Test.
The screen will display "Manual Communicator Test started". When the test is completed, you will be returned to the
<Test Menu>. A Manual Communicator Test requires that at least one daily test in the network be enabled in the
Communicator Programming.
3.
The Manual Communicator Test will be communicated on both the Phone Lines and the Ethernet/Cellular paths if they are
all programmed. Each Manual Communicator Test will alternate between one of the Phone Line paths and one of the
AlarmNet paths.
10.4.8 Manual AlarmNet Registration
1.
From the Main Menu, press 1 for System Tests.
2.
Select 8 to access the Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the
command was sent or not.
10.4.9 Silence Alarms or Troubles
1.
Press SILENCE and enter your code or rotate the key at the prompt.
If an external Silence switch was installed, activating the switch will silence alarms or troubles.
If you already use the System Menus, when you press SILENCE, you do not need to enter your code or rotate the key.
NOTE 1: Alarm and trouble signals that were silenced, but the detector remains un-restored it will un-silence every 4 or 24
hours depending on the user selection until it is restored.
NOTE 2: Multi-Site displays do not allow for silencing multiple sites. If you press SILENCE, it will only locally silence the PZT
built into the annunciator.
10.4.10 Reset alarms
1.
Press RESET and enter your code or rotate the key at the prompt.
If an external Reset Switch was installed, activating the switch will reset the alarms.
If you already use the System Menus, when you press RESET, you do not need to enter your code or rotate the key.
NOTE: The Multi-Site displays do not allow for resetting multiple sites.
Reset Communicator
This option allows the user to Reset the Communicator. The LCD will display:
"Communicator Reset in progress... Please Wait"
You will be returned to the Main Menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. The Communicator Reset is not allowed
if any of the following events are active:
Fire Alarm
10.4.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that the sensitivity levels are in compliance with NFPA 72.
If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detec-
tor enters a CAL MAINT state to indicate that it is approaching an out-of-compliance condition (but it is currently still in com-
pliance).
When a CAL TRBLE condition occurs, the Central Station receives a Detector Trouble Report ("373" and the zone or point
for Contact ID format; "FT" and the zone or point in SIA format). To check the sensitivity for an individual detector, follow
the steps below:
1.
From the Main Menu, press 2 to access the Point Functions.
2.
Press 2 to access the Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
108
Fire Supervisory •
Fire Pre-Alarm •
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
CO Alarm
CO Supervisory
Basic Operation