Programming
9.5.3 Point Programming for 5880 and 5865 Modules
To program for the 5880 or 5865 module points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press ENTER.
5.
Enter the Point Number, then press ENTER.
6.
Press the up or down arrows to select the type (Notification or unused). Press ENTER.
7.
Press the up or down arrows to select the desired Group, then press ENTER.
8.
Edit Module Name. See Section 9.5.3. Or, Press the right arrow to skip the module name edit.
9.
Repeat Steps 1 through 8 for all points.

9.6 System Options

This section of the manual explains how to customize software options that affect general operation of the System. This includes such items
as:
Communication Options • Daytime/Nighttime Sensitivity
Refer to each individual subsection for the complete instructions.
9.6.1 Communication Options
Auto Test Time
To access the Auto Test Time screen:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Select 5 to access the System Options.
4.
From the next Menu, select 1 to access the Communication Options.
5.
Select 1 to access the Auto Test Time.
6.
Enter the hour you want the control panel to send an Automatic Test Report (or press the up or down arrow key), then press ENTER.
7.
Enter the minutes (or press the up or down arrow key), then press ENTER.
8.
Select AM or PM by pressing the up or down arrow key, then press ENTER.
9.
To select the Report Time Interval, press the up or down arrow key. Then, press ENTER.
The Time Interval selections you can choose are the following:
• 24 hour
NOTE: AM and PM are only available if the panel "Clock Options" are set to AMPM mode. Otherwise, the clock is set in the military time and
you cannot select AMPM.
98
Figure 9.6 Programming Points Screen for 5880 and 5865 Modules
• 12 hour
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021
• Holiday Schedule • Telephone and Reporting Account options
• 6 hour
• 4 hour
System Options