Download Print this page

Toshiba GR200 Series Instruction Manual page 554

Hide thumbs Also See for GR200 Series:

Advertisement

in the event suppression detector.
Event suppression
If the status of a device "chatters" for a short time, the SPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the SPOS function;
hence, event suppression can be required to reduce the additional burden created.
2
Signal
On
from device
1
3
Suppressed
On
signal
A
Time.................
Figure 4.1-31 Iterative signals and signals suppressed
Figure 4.1-31 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [SPOS-NELD] is provided so
that the suppression commences at Time B. The setting [SPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [SPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [SPOS01-SPPEN].
BO connection for "Select command On/Off"
(ii)
Figure 4.1-32 exemplifies the connection for the select command On and Off. Suppose that
connection with the BOs is achieved by the PLC function using connection point
"SPOS01_SL_BO_FLG"†; as a result, the " Select command On" and the "Select command Off"
signals are issued at the BOI.
[SPOS-NELD]
4
6
8
On
On
On
5
7
On
On
[SPOS-TELD]
B
- 533 -
On
On
On
On
C
6F2S1915 (0.46)
[SPOS-TELR]
E
D
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200